Compare insulation TGA mass loss, residue and associated temperatures only with matched specimens and test conditions. The curve describes mass changes during that experiment. It does not independently identify a formulation, insulation life or the permissible operating temperature of an assembled busbar.

01

Identify the sampled insulation layer

The public scope of ISO 11358 Part 1, 2022 edition, covers polymer thermogravimetry in programmed temperature or isothermal modes and different atmospheres. State whether the specimen is raw material, cured coating or insulation removed from a finished part.

Record sampling location and preparation. Declare any retained metal, adhesive or other layers. Their contribution changes the mass denominator, so residue from a metal containing assembly specimen cannot directly establish insulation filler content.

02

Keep conditions beside the curves

NETZSCH's application note demonstrates effects from purge flow, crucible geometry and lid configuration. Request gas type and flow, sample mass, crucible and lid status, and the complete temperature program before comparing reported onset temperatures.

Mass loss can also involve volatilization. Require evidence appropriate to the material before identifying evolved species or assigning a step to decomposition. Arrange supplementary analysis when composition is the purchasing question.

03

Define the reported metric and its use

Agree whether comparison uses an extrapolated onset, temperature at a specified mass loss or residue after a defined temperature segment. Retain the method and original curve. Values based on different definitions are not an equivalent ranking.

For PCS insulation, separately verify the actual voltage, thermal history, mechanical state and environment. Reassess report coverage after resin, filler or cure changes. TGA alone does not replace long term aging or finished assembly electrical checks.

04

Frequently asked questions

Does a high mass loss temperature permit continuous energized operation there? A short thermal mass measurement does not establish that permission.

Does matching residue prove an identical formulation? Different materials can have similar residual mass.

05

PCS insulated busbar RFQ inputs

Provide material grade, cure condition, sampling map, original curves and all test conditions. Separate consistency screening, any composition analysis and assembly insulation validation, with the intended purchasing decision stated.

Apply this guide to a project

Use product pages to identify the hardware family and the calculator for early estimates only. Acceptance depends on drawings, operating conditions and project tests.